When the fully automatic capacitance bridge tester measures the capacitance value of a capacitor, the test voltage is simultaneously applied to the standard capacitor and the tested capacitor. The processor collects the current signals flowing through both via sensors and processes them to obtain the capacitance value of the tested capacitor.



Fully Automatic Capacitance Bridge Tester;



Fully Automatic Capacitance Bridge Tester

Product Introduction;

 This capacitance and inductance tester adopts a bridge circuit structure, with the standard capacitor and the tested capacitor serving as the two arms of the bridge circuit. When measuring the capacitance value of a capacitor, the test voltage is simultaneously applied to the standard capacitor and the tested capacitor. The processor collects the current signals flowing through both via sensors and processes them to obtain the capacitance value of the tested capacitor.

Product Features;

(1) Measurement of single-phase capacitors:

For single-phase capacitor testing, connect one end of the red test lead to Ua and the other end with the test clamp to one busbar; connect one end of the black test lead to Uo and the other end to another busbar. Connect the output wire of the clamp CT to the Ia terminal of the instrument. Clamp the clamp CT onto the capacitor lead end connected to the busbar with the red test clamp. When connecting, pay attention that the end of the current clamp marked with "P" faces the capacitor direction and is clamped onto the capacitor; otherwise, the measured phase angle will be incorrect.

If multiple single-phase capacitors in a capacitor bank need to be tested, after testing the first capacitance value, press the return key. The voltage test leads do not need to be moved. Simply open the current clamp of the test current and clamp it onto the next capacitor, then press the confirm key to test. This greatly improves testing speed, which is the biggest feature of this instrument.

(2) Measurement of three-phase delta (Δ) connected capacitors:

This is the wiring method for measuring three-phase delta-connected capacitors. Connect the measurement leads from the instrument's measurement output terminals according to the color codes. Clamp the yellow clamp onto phase A of the busbar, the green clamp onto phase B of the busbar, and the red clamp onto phase C of the busbar. Then insert the three current measurement leads into the Ia, Ib, and Ic terminals of the instrument respectively and tighten them. Correspondingly, clamp the clamp sensors onto the incoming leads of phases A, B, and C of the high-voltage capacitor bank. Pay attention to whether the direction of each clamp current transformer is correct; otherwise, it will cause errors in the phase angle of the measured capacitance.

(3) Measurement of three-phase Y-connected capacitors:

The wiring method for three-phase Y-connected capacitors is the same as that for delta-connected capacitors, except that during measurement, select the three-phase Y-connected capacitor measurement. No specific introduction will be provided here.

(4) Measurement of three-phase Yn-connected capacitors:

Figure 6 shows the wiring method for measuring three-phase Yn-connected capacitors. Connect the measurement leads from the instrument's measurement output terminals according to the color codes. Clamp the yellow clamp onto phase A of the busbar, the green clamp onto phase B of the busbar, the red clamp onto phase C of the busbar, and the black clamp onto phase N of the busbar. Then insert the three current measurement leads into the Ia, Ib, and Ic terminals of the instrument respectively and tighten them. Correspondingly, clamp the clamp sensors onto the incoming leads of phases A, B, and C of the high-voltage capacitor bank. Pay attention to whether the direction of each clamp current transformer is correct; otherwise, it will cause errors in the phase angle of the measured capacitance.



Fully Automatic Capacitance Bridge Tester

Product Parameters;

(1) Capacitance measurement range: 0.1 μF to 3,300 μF

(2) Reactive power measurement range: 5 to 20,000 kvar

(3) Measurement accuracy: ±(1.0% reading + 0.02 μF)

(4) Resolution: 0.001 μF
Current measurement

(1) Current measurement range: 0 to 20 A

(2) Measurement accuracy: ±(3.0% reading + 0.05 A)

(3) Resolution: 0.01 A
 c. Inductance measurement

(1) Inductance measurement range: small inductance mode 200 μH to 5 mH
                   large inductance mode 5 mH to 10 H

(2) Inductive reactance measurement range: 100 mΩ to 20 kΩ

(3) Measurement accuracy: ±(3.0% reading + 0.05 mH)

(4) Resolution: 0.01 mH
      d. Resistance measurement range:
           (1) Resistance measurement range: small resistance mode 50 mΩ to 1 Ω
large resistance mode 1 Ω to 20 kΩ
           (2) Measurement accuracy: ±(3.0% reading + 0.05 Ω)
           (3) Resolution: 0.01 Ω 