Main Features



Strictly comply with technical specifications and unified standards of national power supply departments.



1. Adopts high-performance digital signal processor (DSP) and very large scale integrated circuit (VLSI) chips, providing powerful processing capabilities.



2. Multiple trigger functions. It can trigger using input signals, meaning that once a signal appears on the input channel, the acquisition device will automatically trigger and complete the recording and acquisition function. This eliminates the need for external trigger signals and resolves synchronization issues between trigger and measured signals. Additionally, the internal trigger pulse width can be programmatically adjusted to avoid false triggering caused by interference spikes.



3. High-speed, high-precision data sampling with adjustable sampling rate and time (sampling speed programmable from 25us to 100us), adaptable to various measurement requirements.



4. Long data recording time, meeting various switch testing requirements.



5. Surface mount technology, with electromagnetic interference absorption components on main signal circuits, providing excellent electromagnetic compatibility, suitable for harsh electromagnetic environments with strong anti-interference capability.



6. Multiple acquisition channels. The device has 3 travel measurement channels and 7 contact measurement channels, allowing simultaneous 3-channel travel measurement.



7. Automatic calculation of various parameters, with manual calculation option.



8. Out-of-range alarm. Automatically alarms when test values exceed preset thresholds.



9. System automatically monitors the open/close state of the switch and displays it at the top of the program window.



10. Built-in operating power supply, can directly store energy and operate the switch.



11. All test functions and algorithms comply with IEC standards.



Technical Specifications



1. Time Measurement



Number of contacts measurable simultaneously: ≤12



Process setting time: 0~6 seconds



Resolution: 0.1ms



2. Switch opening distance, overtravel, and bounce amplitude measurement



Range: <500mm



Resolution: 1mm



3. Measurement Error



Time measurement error: ±1%



Travel measurement error: ±1%



4. Operating Conditions



Operating voltage: AC220V±10%



Frequency: 50HZ



Power consumption: ≤60W



Operating ambient temperature: -10℃~40℃



Operating ambient humidity: ≤90%RH



Dimensions: 400×350×200mm



Weight: 7kg