Product Functions:
1) With positive/reverse wiring, internal/external standard capacitor, internal/external high voltage multiple working modes, integrated structure, can perform various conventional dielectric loss tests without any external auxiliary equipment.
(2) With four-channel positive wiring mode, convenient for transformer bushing dielectric loss tests.
(3) With external standard capacitor interface, automatically tracks external test power frequency 40Hz~70Hz, supports power frequency and series resonance power for large-capacity high-voltage dielectric loss tests.
(4) With loop poor contact discharge indication function, to facilitate judging whether wiring is reliable.
(5) With CVT self-excitation method measurement function, C1/C2 can be measured simultaneously with one wiring, automatically compensates for bus grounding and standard capacitor voltage division effects, no need to change wires or connect any external accessories, and high-voltage connecting wires can be dragged on the ground.
(6) With CVT ratio function, can measure CVT ratio, polarity, and phase error.
Product Aliases
Dielectric loss tester, anti-interference dielectric loss tester, fully automatic dielectric loss tester, manufacturer of variable frequency dielectric loss tester, manufacturer of variable frequency dielectric loss tester, anti-interference dielectric loss tester, fully automatic dielectric loss tester
Internal Booster Output Capability
Output Voltage Rated Output Current
5kv 7.5kv 10kv 100mA
1.5kv 2.25kv 3kv 300mA
0.5kv 0.75kv 1kv 500mA
External Connection Mode
“External booster” mode maximum test voltage 10KV
“External Cn” mode (external high voltage, external standard capacitor) maximum test voltage determined by standard capacitor and test object (Umax=Imax/ωC)
Standard circuit maximum current 50mA (In=UωCn)
Test object circuit maximum current 2A (Ix=UωCx)
Operation Precautions:
1. When using, the instrument grounding terminal must be reliably grounded.
2. Only when the instrument power is turned off and the internal high voltage allow switch is set to “Off” position, contacting the rear of the instrument and its measurement cables with the test object is considered safe.
3. During measurement, it is strictly prohibited to operate the “Test Voltage” selection switch.
4. In positive wiring method, the UH terminal is high voltage; in reverse wiring method, the IX terminal is high voltage. When using, must keep sufficient distance between high-voltage cables and ground according to actual conditions, except for special cables when test voltage is below 10KV.
5. Do not replace fuse tubes that do not match the panel indication values.
6. When using, use the cables provided by the manufacturer as much as possible to ensure measurement accuracy.