Aliases of Transformer Ratio Automatic Tester
Transformer ratio group tester, three-phase ratio tester, intelligent ratio tester, transformer three-phase ratio tester, intelligent ratio and impedance tester.
English
Technical characteristics of Transformer ratio automatic testing instrument
1. Fully automatic ratio measurement, no parameter setting required, automatically completes three-phase ratio and group tests.
2. Uses precision electronic components, measurement accuracy is stable and reliable for long-term use.
3. Can measure transformers with connection groups such as Y/y, Y/d, D/y, D/d, Zn/y, Zn/d.
4. Can measure three-phase transformer groups and single-phase transformer polarity.
5. The total number of tap points can be set arbitrarily; the instrument automatically calculates and stores data based on tap points. No need for repeated input or manual calculation.
6. Accurate measurement, fast speed, continuous three-phase ratio measurement takes only a few seconds.
7. Can store or print all measurement results; the instrument has a built-in non-volatile memory to save measurement data for long-term and can be reviewed at any time.
8. All Chinese menu and operation prompts, intuitive and convenient.
9. Non-volatile calendar and clock functions.
10. Dedicated computer input keyboard, 100,000 times of fault-free operation.
11. The shell is sealed with professional engineering plastic, waterproof, moisture-proof, and shockproof.
Main Functions and Features
1. Automatically measure wiring group. 2. Automatically perform group transformation. 3. Automatically switch phase sequence. 4. Automatically switch range. 5. Automatically calibrate the meter. 6. After inputting the standard ratio, it can automatically calculate the relative error. 7. After one measurement is completed, automatically cut off the test voltage. 8. Set data, measurement results are automatically saved, and previous data can be viewed. 9. For measuring on-load transformers, only input the ratio once. 10. Equipped with serial R232 interface. 11. Equipped with a micro printer, can also directly print out data results.
Main Technical Indicators
1. Ratio measurement range: 1—10000 2. Group: 1—12 points 3. Accuracy: 1-1000 0.2 class, 1000-10000 0.5 class 4. Power supply: AC220V ±10%, 50HZ 5. Operating ambient temperature: -5℃ ─ 40℃ 6. Operating ambient humidity: <85% 7. Volume: 430×320×215mm3 8. Weight: 8Kg
Operation Method
1. Wiring: Turn off the power switch of the instrument, and wire according to the following method. Single-phase transformer Three-phase transformer Instrument Transformer Instrument Transformer A A A A B X B B C Not connected C C a a a a b x b b c Not connected c c The neutral point of the transformer is not connected to the instrument or ground. Connect the ground wire of the instrument. Insert one end of the power cord into the power socket on the instrument panel, and connect the other end to AC 220V power. Note: Do not reverse the high and low voltage connections of the transformer! Set wiring method Set standard ratio Start data measurement View historical data ↑: Select Confirm: Execute 2. Turn on the power switch of the instrument, and after a moment the main menu appears on the LCD screen, as shown below. The selected menu is displayed in reverse (black background with white text). At this time, press the "↑" key to select the function menu, and press "Confirm" to execute the corresponding function. Note: Press and release the key for one key input. Set wiring method Wiring: Yy Set standard ratio Start data measurement View historical data ↑: Select Confirm: Save 3. Wiring setting: After entering the wiring method setting, the LCD screen displays as follows. At this time, press the "↑" key to select the wiring method, and press "Confirm" to save the wiring method and return to the main menu. Set wiring method Set standard ratio Ratio=25.000 Start measurement data View historical data →: Shift ↑↓: Increase/Decrease Confirm: Save 4. Set standard ratio: After entering the standard ratio setting, the LCD screen displays as follows. At this time, press the "→" key to select the data digit, and the selected digit is displayed in reverse. Press "↑" and "↓" keys to modify the data. After selecting a digit, press "↑" and "↓" keys, the digit changes cyclically from 0 to 9. If it is the first digit, it only changes cyclically from 1 to 9, and 0 will not appear. After selecting the decimal point, press "↑" and "↓" keys to move the decimal point cyclically. Set wiring method Set standard ratio Adjustment ratio=0.00% Start measurement data View historical data →: Shift ↑↓: Increase/Decrease Confirm: Save If the transformer has taps, the standard ratio set here is the standard ratio of the middle tap. After pressing "Confirm" to save the ratio, the LCD screen displays as follows. The setting method for the adjustment ratio is the same as that for the standard ratio. If the transformer has taps, set according to the actual value; otherwise, set to 0.00%. After pressing "Confirm" to save the adjustment ratio, return to the main menu. 5. After warming up for 5 minutes, select "Start data measurement" and press "Confirm". The display is as follows: Wiring=Yy? Ratio=25.000? →: No Confirm: Yes ↑↓: Change tap The ratio value displayed on the screen is the actual standard ratio needed for this measurement. Press "↑" and "↓" keys to modify this value. Each modification step = set standard ratio × adjustment ratio. After measurement is completed, the display is as follows: 3rd time Total 3 times Group: 12 points AB: 25.008 0.03% BC: 25.010 0.04% CA: 25.000 0.00% ↑: Page up →: Print Confirm: Return After each measurement, the instrument automatically saves the data, up to 30 data items. When exceeding 30, the current data is stored as the 30th, and the first data is cleared, i.e., first in, first out. The first line on the left shows the position of the current data in the historical data, and on the right shows the number of historical data. The second line is the group. The third line on the left is the ratio of phase AB, and on the right is the relative error of phase AB, and so on. If measuring a single-phase transformer, only the first three lines are displayed. If the relative error of the measured ratio is greater than 10%, display ">10%"; if less than -10%, display "<-10%". Press "↑" to view data. Press "←" to enter the print menu, can print current data, print all data, and can clear all historical data. Press Confirm to return to the main menu.
Precautions
1. During measurement, do not touch the test object.
2. If the test leads are short-circuited or the high and low voltage wires are reversed, the fuse will blow. After the fuse blows, if measurement is performed, it will stop after displaying "Measuring, please wait!". Please turn off the power, replace the fuse with the same capacity, and then measure again.
3. The test leads must have good contact. The instrument should be properly grounded!
4. The working place of the instrument should be far away from strong electric fields, strong magnetic fields, and main frequency equipment. The power supply interference should be as small as possible; it is advisable to use lighting lines. If the power interference is still large, an AC purified power supply can be used to power the instrument. The capacity of the AC purified power supply should be greater than 200VA.
5. During operation, if the LCD display is disordered, all keys have no response, or the measured value is far from the actual value, press the reset key or turn off the power and then restart the operation.
6. If the display has no characters or the color is too light, adjust the brightness potentiometer to a suitable value.
7. When working in dark places, the backlight can be turned on. To reduce the power consumption of the display, the backlight is not very bright.
8. The instrument should be stored in a dry and ventilated place.