Automatic Transformer Ratio and Group Tester (with Charging Function)Safety Measures
1. Before using this instrument, be sure to read this manual carefully.
2. The operator of the instrument should have common knowledge of electrical equipment or instruments.
3. The instrument should be reliably grounded when in use.
4. The power supply of this instrument is internal lithium-ion battery or AC220V±10% 50/60HZ±1HZ
5. The instrument outputs high voltage, so pay attention to safety to prevent electric shock.
6. This instrument can be used indoors and outdoors, but should avoid use in harsh environments such as rain, corrosive gas, excessive dust, high temperature, direct sunlight, etc.
7. The instrument should avoid severe vibration.
8. Maintenance, care, and adjustment of the instrument should be carried out by professionals.
9. The yellow, green, red, and black test clips correspond to the A, B, C, and O of the transformer respectively. Do not reverse the high and low voltage cables.
10. For single-phase measurement, only use the yellow and black clips. Do not use them incorrectly, and unused test clips should be left suspended.
Automatic Transformer Ratio and Group Tester (with Charging Function)Product Features
1. Wide test range, up to 0.9 to 10000.
2. Fast test speed, completes three-phase test in 11 seconds.
3. Can test CT, PT, CVT, and Z-connected transformers.
4. Has blind test ratio and group test functions.
5. Multiple measurement modes, more convenient for fault diagnosis.
6. Non-volatile clock and date display, data storage of 480 groups, data not lost on power failure.
7. Large screen color LCD display, data clear and easy to read. RS485 communication interface and U disk storage interface.
8. The instrument has high and low voltage reverse connection protection, transformer short circuit, inter-turn short circuit protection, and power supply misconnection to 380V protection.
9. Thermal printer printing function, fast and silent.
10. Small size and light weight.
|
|
|
|