Automatic Transformer Turns Ratio and Group Tester (with Charging Function) Safety Measures
1. Before using this instrument, be sure to read this manual carefully.
2. The operator of the instrument should have general knowledge of electrical equipment or instruments.
3. The instrument should be reliably grounded when in use.
4. The power supply for this instrument is an internal lithium-ion battery or AC220V±10% 50/60HZ±1HZ
5. The instrument outputs high voltage, so pay attention to safety and prevent electric shock.
6. This instrument can be used indoors and outdoors, but avoid use in harsh environments such as rain, corrosive gases, excessive dust, high temperature, direct sunlight, etc.
7. The instrument should avoid severe vibration.
8. Maintenance, care, and adjustment of the instrument should be carried out by professionals.
9. The yellow, green, red, and black test clips correspond to the transformer's A, B, C, and O respectively. Do not reverse the high and low voltage cables.
10. For single-phase measurement, only use the yellow and black clips. Do not use the wrong ones, and keep unused test clips suspended.
Automatic Transformer Turns Ratio and Group Tester (with Charging Function) Product Features
1. Wide test range, up to 0.9 to 10000.
2. Fast test speed, completing three-phase test in 11 seconds.
3. Can test CT, PT, CVT, and Z-connected transformers.
4. Has blind test function for turns ratio and group testing.
5. Multiple measurement modes for easier fault diagnosis.
6. Non-volatile clock and date display, data storage for 480 groups, data not lost on power failure.
7. Large screen color LCD display with clear and readable data. RS485 communication interface and USB storage interface.
8. The instrument has high/low voltage reverse connection protection, transformer short circuit and inter-turn short circuit protection, and protection against accidental connection to 380V power supply.
9. Thermal printer printing function, fast and silent.
10. Small size and light weight.