I. Transformer Capacity and No-load/Load Tester ZYYB Features
1. Can accurately measure the capacity of various distribution transformers, passive measurement, convenient and accurate.
2. Can measure the no-load current, no-load loss, short-circuit voltage, short-circuit loss, and zero-sequence impedance of various types of transformers.
3. Automatically performs waveform distortion correction, temperature correction, voltage correction (no-load test under non-rated voltage), and current correction (short-circuit test under non-rated current). The operator only needs to input the correction index based on the transformer type, and the instrument automatically calculates the corrected results, making it very suitable for units that do not have conditions for short-circuit tests on slightly larger capacity transformers.
4. Allows external voltage transformers and current transformers to be connected for extended range measurement, and can measure test objects of any parameters.
5. Wide voltage range: maximum voltage measurement up to 750V, ensuring accuracy without switching gears. It will not damage the instrument due to incorrect gear selection.
6. Large screen, high-brightness LCD display, full Chinese menu and operation prompts for friendly human-machine interaction, touch buttons make operation easier.
7. Users can print the test data at any time through the micro printer.
II. Transformer Capacity and No-load/Load Tester ZYYB Technical Specifications
1. Input Characteristics
Active part:
Voltage measurement range: 0~10V
Current measurement range: 0~10A
Passive part:
Voltage measurement range: 0~750V wide range.
Current measurement range: 0~50A, all internal automatic range switching.
2. XJYB Active Transformer Capacity Characteristic Tester Accuracy
Voltage, current, frequency: ±0.2%
Power: ±0.5% (CosΦ>0.1), ±1.0% (0.02< SPAN>Φ<0.1)
3. Operating temperature: -10℃~ +40℃
4. Power supply: AC 160V~400V
5. Insulation: (1) Insulation resistance between voltage/current input terminals and the case ≥100M?.
(2) The power supply input terminal withstands a power frequency of 2KV (RMS) for 1 minute against the case.
6. Dimensions: 40cm×32cm×18cm