Test Method
Edit
The specific method is chosen by the manufacturer based on the test equipment available. If the test equipment allows, the specified test voltage can be applied directly to the primary winding for excitation. If limited by the frequency multiplier transformer, the PT's own ratio can be utilized to apply sufficient excitation voltage from the secondary winding, causing the primary winding to induce the specified test voltage value.
Capacitance Rise Effect
Edit
In practice, the induced overvoltage test of a voltage transformer involves connecting a capacitive voltage divider to the high-voltage terminal of the primary winding to measure the induced voltage, then exciting the secondary winding with a medium-frequency power supply voltage several times the 50Hz frequency. When the reading on the low-voltage indicator of the divider reaches the specified requirement, it should be maintained for a certain duration. At this time, the primary winding of the voltage transformer carries a capacitive load.


