b) Same-phase asynchrony: refers to the time difference in the opening (closing) times of the same-phase breaks for switches with more than six breaks.
c) Bounce time: refers to the cumulative time of all contacts and separations (i.e., bouncing) between the moving and static contacts of the switch during the closing process (i.e., the time from the first contact to complete contact).
d) Opening time: the time interval from the moment the opening trip coil is energized to the moment when all pole arc contacts separate, for a circuit breaker in the closed position.
e) Closing time: the time interval from the moment the closing circuit is energized to the moment when all pole contacts touch, for a circuit breaker in the open position.
f) Reclosing time: during the reclosing cycle, the time interval from the starting moment of the opening time to the moment when all pole contacts touch.
g) Just-opening (closing) speed: refers to the average speed of the moving contact relative to the static contact within a specified time or distance. For example, with 10ms, for opening, it is the average speed within 10ms after opening; for closing, it is the average speed within 10ms before closing.
h) Opening distance: refers to the distance from the start of the open state to the moment when the moving contact just touches the static contact.
i) Maximum opening (closing) speed: refers to the maximum value of the instantaneous speed during opening (closing). Generally, this value should appear at the moment when the switch just opens or closes, which can be determined from the speed-travel curve.
j) Average opening (closing) speed: refers to the ratio of the travel of the moving contact to the time during the entire operation process.