Four-Level Acceptance Test Equipment - Heterodyne Dielectric Loss Tester Product Features



(1) It has multiple working modes: positive/reverse wiring, internal/external standard capacitor, internal/external high voltage, integrated structure, can do various conventional dielectric loss tests without external auxiliary equipment.



(2) LCD display, menu operation, rich test data, automatically distinguish capacitive, inductive, resistive test objects, built-in micro printer for printout.



(3) It has an external standard capacitor interface, can connect an external oil cup for precision insulating oil dielectric loss test, can connect external solid material measuring electrodes for precision insulating material dielectric loss test, and can also connect an external high-voltage standard capacitor for high-voltage dielectric loss test.



(4) Automatically recognizes 50Hz 60Hz system power supply, supports generator power supply, even if the frequency fluctuates greatly, it can measure normally.



(5) Built-in series and parallel dielectric loss measurement models for easy instrument calibration.



(6) Can store 255 sets of measurement data.



(7) When measuring with CVT self-excitation method, C1/C2 can be measured simultaneously with one wiring, automatically compensating the influence of busbar grounding and standard capacitor voltage division, no need to change wiring or connect any external accessories.



(8) Chinese graphic menu, large-screen backlit LCD display is clearer, real-time monitoring of current and voltage.



(9) Optimized circuit design makes the accuracy and stability of positive/reverse wiring consistent.



(10) Automatically recognizes external high-voltage test power supply frequency 40Hz~70Hz, supports power frequency power supply, variable frequency power supply and series resonance power supply for large-capacity high-voltage dielectric loss test.



Four-Level Acceptance Test Equipment - Heterodyne Dielectric Loss Tester Internal Connection Method



      Test Voltage               Test Object Capacitance



      5KV    7.5KV  10KV      3PF~40000PF



      1.5KV  2.25KV  3K       10PF~0.35μF



      0.5kv  0.75kv  1kv      30PF~1.5μF



2.3.2.2 External Connection Method



   “External Step-up Transformer” method test voltage 10KV



   “External Cn” method (external high voltage, external standard capacitor) test voltage is determined by standard capacitor and test object (Umax=Imax/ωC)



     Standard circuit maximum current 50mA (In=UωCn)



     Test circuit maximum current 2A (Ix=UωCx)



CVT ratio measurement:



Ratio measurement accuracy: ±reading×1% Ratio measurement range: 10~99999



Phase measurement accuracy: ±0.1° Phase measurement range: 0~359.9°



Measurement time: about 40s, depending on measurement method



Input power: 180V~270VAC, 50Hz±1%, mains or generator power supply



Computer interface: standard RS232 interface



Printer: Weihuang A7 thermal micro printer



Ambient temperature: -10℃~50℃



Relative humidity: <90%



Dimensions: 460×360×350mm



Instrument weight: 28kg