3KVA5KVA50KV Power Frequency Withstand Voltage Test Device
Product Overview
It is a new type of high-voltage testing equipment. This series of products adopts a single-frame core-type iron core structure, with the primary winding and high-voltage winding coaxially wound on the iron core, thereby reducing leakage flux and increasing coupling between windings. The overall structure of the product is compact, with strong versatility, and is easy to use and carry. It is suitable for power systems and power users to test the insulation performance of various high-voltage electrical equipment on site, and is an essential test instrument for power equipment testing and preventive tests.
The light high-voltage test transformer can be used not only for AC power frequency withstand voltage tests, but also can be assembled into a DC high-voltage test device by equipping with capacitors, silicon stacks, and high-voltage DC microammeters of the same voltage level and capacity, allowing measurement of high-voltage DC leakage current.
Product Structure
The iron core is of single-frame type. The coil adopts a concentric cylindrical multi-layer tower structure, with the primary low-voltage winding wound on the iron core and the secondary high-voltage winding wound outside the low-voltage winding. This coaxial arrangement reduces coupling loss between windings. The high-voltage silicon stack is encapsulated in the bushing with a special process, and the product shell is made into an octagonal structure that matches the core well, presenting an overall beautiful and elegant appearance.
Working Principle
1. Single-phase transformer, connection group label II. The working process of a single high-voltage test transformer: AC 220V (380V for 10KVA and above) is connected to the power control box (console), and the voltage is adjusted to 0~200V (0~400V for 10KVA and above) by the auto-transformer (external for 50KVA and above) inside the power control box (console) to the primary winding of the test transformer. According to the principle of electromagnetic induction, the required high voltage for testing can be obtained on the high-voltage winding of the test transformer.
Technical Specifications
1. 3KVA5KVA50KVPower Frequency Withstand Voltage Test Device, Operating Environment Conditions
Ambient temperature not higher than +45℃, not lower than —20℃;
Relative air humidity not greater than 90%;
Altitude not exceeding 2000 meters;
2. Working Voltage
The input voltage of the power control box (console) is power frequency 220V or 380V, with relative error not exceeding ±10%; (the specific operating voltage is selected according to the user's specified test transformer specification)
35KVA/50KV parameters;
Rated capacity: 5KVA
High-voltage output voltage: 50KV High-voltage output current: 100mA
Input voltage: 0-200V
Input current: 25A
5KVA/220V Control Console (Operation Box)
Rated capacity: 5KVA
Input voltage: 220V 50HZ ±10%
Output voltage: 0-230 continuously adjustable
Output current: 25A
Meter voltage: 100V
Meter indication: AC50KV
Meter current: 0-25A
This control console (box) has functions such as zero position protection, overcurrent adjustment, overcurrent protection, time adjustment, and time alarm.