Fully Automatic Volt-Ampere Characteristic Tester Test Operation Method and Procedure



7.2 Volt-Ampere Characteristic and Error Curve Test

In the main interface, click the "Test" menu, and in the pop-up submenu, click "Volt-Ampere Characteristic Test" command to open the Volt-Ampere Characteristic and Error Curve Test window (as shown in Figure 33 below)

 Volt-Ampere Characteristic and Error Curve Test

                           Figure 33

7.2.1 Interface Parameter Description

Segmentation Point Current Value: During the test, to ensure that the points before and after the inflection point of the volt-ampere characteristic curve are distributed reasonably, a segmentation point is set. Before and after this point, tests are conducted with two different current step sizes. The segmentation point current value is set based on estimated value or measured inflection point value, range (0 - 20) A.

Step Size Before Segmentation: The step current step size before the segmentation point, range (0.001 - 2.000) A

Step Size After Segmentation: The step current step size after the segmentation point, range (0.001 - 2.000) A

Maximum Output Voltage: The maximum voltage that the secondary side of the current transformer can withstand, range (0 - 1500) V.

Maximum Output Current: The maximum current that the secondary side of the current transformer can withstand, range (0 - 20) A.

Standalone Test: When testing with the built-in voltage regulator of the device, click "Standalone Test".

External Voltage Regulator Test: When testing with an external voltage regulator is needed, click "External Voltage Regulator Test".

7.2.2 Test Method

7.2.2.1 Volt-Ampere Characteristic Curve

The test principle and wiring method of the fully automatic volt-ampere characteristic tester are the same as those of the standalone unit. After wiring is completed, click "Start Test" to begin the test. At this time, the device automatically increases voltage and current step by step according to voltage, current, and step size values for testing. Each measured point will be automatically displayed in the data display box with voltage and current values, and the volt-ampere characteristic curve will be automatically plotted. During the test, you can click "Stop Test" at any time to terminate the test.

7.2.2.2 Error Curve

After completing the volt-ampere characteristic test, set "Secondary Rated Current" and "Error Type" respectively, then click "Calculate Error Curve" option to calculate and display error data based on the measured volt-ampere characteristic data, and automatically plot the 5% or 10% error curve.

7.3 Transformation Ratio Polarity Test, Secondary Load, and Demagnetization Test

In the main interface of the fully automatic volt-ampere characteristic tester, click the "Test" menu, and in the pop-up submenu, click "Transformation Ratio Polarity Test" to open the Transformation Ratio Polarity Test, Secondary Load Test, and Demagnetization Test window (as shown in Figure 34 below)

Transformation Ratio Polarity Test, Secondary Load, and Demagnetization Test

Figure 34

7.3.1 Transformation Ratio Polarity Test

7.3.1.1 Parameter Settings

Maximum Test Current Applied on Primary Side: The current to be applied to the primary side of the current transformer during transformation ratio polarity test, range 0 - 600A.

Secondary Rated Current: The rated current of the secondary side of the current transformer, 1A or 5A.

Primary Current: The actual current value applied on the primary side during the transformation ratio polarity test.

Secondary Current: The actual current value measured on the secondary side during the transformation ratio polarity test.

Transformation Ratio: The actual transformation ratio calculated based on the actual currents measured on the primary and secondary sides during the transformation ratio polarity test.

Polarity: The actual polarity measured during the transformation ratio polarity test.

"Keep output for a certain time when testing secondary circuit" is used to maintain the primary output current for a period of time. The length of this time is related to the current value; the larger the current, the shorter the time.

7.3.1.2 Test Method

After setting the parameters, click "Start Test" to perform the test. After the test is completed, the transformation ratio polarity value will be automatically displayed. During the test, you can click "Stop Test" at any time to terminate the test.

7.3.2 Secondary Load Test

After setting the secondary rated current value, click "Start Test" to perform the test. After the test is completed, the secondary impedance and secondary load will be automatically displayed. During the test, you can click "Stop Test" at any time to terminate the test.

7.3.3 Demagnetization Test

After setting the "Current Value Applied on Primary Side", click "Start Test" to complete the demagnetization test. During the test, you can click "Stop Test" at any time to terminate the test.