Loop Resistance Tester with Printing


Precautions








































Fault Phenomenon Cause Analysis Troubleshooting Remarks
No display on power-on 1) Power not connected Connect power supply When replacing the fuse, use the same type; do not substitute with other types.
2) The instrument's 5A fuse is not installed properly or is open Reinstall or replace the fuse    
Output current cannot reach 200A 1) Test leads too long, i.e., wire cross-section too small Replace with wires of larger cross-section  
No current output 1) Device under test is open circuit Check the device

Troubleshoot
 
Open circuit fault in test loop Check the test loop and clear the open circuit fault    





1. Before turning on the power switch, ensure the test button is released (not in test state) and turn the current adjustment knob counterclockwise to the "zero" position.



2. The instrument should be placed indoors in a dry, ventilated area free from corrosive gases.

3. After testing, wait until the power is fully discharged before removing test leads and other equipment.

Transportation and Storage


1. Transportation

When the equipment needs to be transported, it is recommended to use the company's instrument packaging wooden case and shock-absorbing materials to avoid unnecessary damage during transit and prevent unnecessary losses.

When the equipment is transported without a wooden case, stacking is not allowed. When using the company's instrument packaging case, the maximum stacking layers allowed is two.

During transportation, the instrument panel should face upward.

2. Storage

The equipment should be placed indoors in a dry, dust-free, ventilated area free from corrosive gases. Without wooden case packaging, stacking is not allowed.

When storing, the panel should face upward. Place moisture-proof materials under the equipment to prevent dampness.