Inherent opening (closing) time

            Opening (closing) phase-to-phase difference within the same phase

            Opening (closing) phase-to-phase difference between phases

            Closing (opening) bounce time (bounce count)

            Test range: 0.01ms~10000ms

            Accuracy: within 1ms~100ms accuracy 0.1%±2 digits, greater than 100ms accuracy 0.5%±2 digits

  2. Speed measurement: just opening (just closing) speed

            Average speed over specified time period (stroke segment or angle segment)

            Speed measurement range: 1mm sensor 0.01~25.00m/s,

            0.1mm sensor 0.001~2.50m/s, 360° angle sensor 0.01~25.00m/s,  universal sensor: 0.01~10.00m/s

  3. Stroke measurement: moving contact stroke (stroke)   contact stroke (opening distance)  overtravel or return stroke (overtravel)

  4. Sensor measurement range:

            Linear displacement sensor 50mm, resolution: 0.1mm, stroke 0.1~50mm

            Linear displacement sensor 300mm, resolution: 0.1mm, stroke 10~300mm (optional)

            Linear displacement sensor 500mm, resolution: 1mm, stroke 10~500mm (optional)

            360-line sensor: 360°, resolution: 0.25°, stroke 1mm~1000mm     

  5.  Current measurement: displayed current is the maximum current value of the opening (closing) coil

  6. Display: 320×240 LCD screen, contrast adjustable

  7. Data storage: can store 100 sets of measurement data

  8. Printer: high-speed thermal printer

  9. Instrument power supply: AC/DC 220V ± 10%; 50Hz ± 2%

  10. DC power supply: output voltage: 25~265V continuously adjustable, output current: ≤ 20A (short time)

  11. Main unit dimensions: 360×250×140mm

  12. Operating environment: -10℃~+50℃

  13. Relative humidity: ≤90%